28 - Modules Programming Guide
DGP-ACM12
4-Wire Access Control Module
U = Default setting
Section [001] Partition Assignment
Option OFF ON
[1] Partition 1 N Disabled U Enabled
[2] Partition 2 N Disabled U Enabled
[3] Partition 3 N Disabled U Enabled
[4] Partition 4 N Disabled U Enabled
[5] Partition 5 (EVO 192 only) N Disabled U Enabled
[6] Partition 6 (EVO 192 only) N Disabled U Enabled
[7] Partition 7 (EVO 192 only) N Disabled U Enabled
[8]
Partition 8
(EVO 192 only) N Disabled U Enabled
Section [002] General Options 1
Option OFF ON
[1]
Tamper Input
U Disabled N Enabled
[2]
Battery Charging Current
U 350mA N 800mA
[3]
Reader’s red LED to follow partition’s status
N Disabled U Enabled
[4]
Reader’s beeping to follow partition’s status when option
[3]
is ON
N Disabled U Enabled
[5]
Card activates door unlocked schedule
N Disabled U Enabled
[6] Door will relock U Immediately N When closed
[7]
Reader’s green LED for Access Granted
N Disabled U Enabled
[8]
Unlock on Request for Exit (REX)
N Disabled U Enabled
Section [003] General Options 2
Option OFF ON
[1] Door Left Open Alarm U Disabled N Enabled
[2] Door Left Open Pre-alarm N Disabled U Enabled
[3] Door Left Open Alarm N Silent U Audible
[4] Door Left Open Alarm follows U Alarm Restore N Beep Timer
[5] Door Forced Open Alarm U Disabled N Enabled
[6] Door Forced Alarm N Silent U Audible
[7] Door Forced Alarm follows U Alarm Restore N Beep Timer
[8] Reader Access Feedback NVisual U Visual and Audible