Modules Programming Guide - 15
DG467 V1.0
360° Ceiling Mounted Motion Detector Module
Operational Modes
The DG467 can function in two different operational modes: combus mode or relay mode. This option can only be configured using the J4
jumper:
Relay Mode: (J4 = OFF)
When set to Relay Mode, the DG467 functions as would any standard motion detector by communicating its alarm and tamper signals
via relays. The GRN and YEL terminals are not used in relay mode. In Relay Mode, the detector’s settings can only be modified using
the jumpers (see figure 1).
Combus Mode: (J4 = ON)
When set to combus mode, the DG467 communicates alarm signals, tamper signals, data and detector settings via the panel’s 4-wire
combus. The detector’s relay output always remains active even when set to combus mode and can be used to activate other
devices.
In combus mode, the motion detector can be modified using the jumpers or by entering module programming mode.
In combus mode, the DG467 will respect the most recent modification whether it is made through the jumpers or through section
programming. As a result, current jumper positions may not represent actual settings. All settings are stored in the DG467 even after
it has been powered down
U = Default setting
Section [001] General Options
Options OFF ON Manual Jumper Setting
[1]
Signal Processing Mode
N Dual Edge U Single Edge OFF = Dual Edge J3
ON = Single Edge J3
[2]
LED Settings
N Disabled U Enabled OFF= Disabled J1
ON = Enabled J1
[3]
Movement Without Alarm
N Disabled U Enabled NN/A
[5]
Tamper Recognition
U Disabled N Enabled NN/A
Section Status Display Mode Description Default Manual Jumper Seeting
[002] __/__/__ 000 UVery low shield (high sensitivity) J2 OFF = High Shield
__/__/__ 001 Low shield
n/a
J2 ON = UVery low shield
__/__/__ 002 Normal shield
n/a
n/a
__/__/__ 003 High shield
n/a
n/a
Section Voltage Meter
[900] Displays [3-digit number] which represents input voltage x 10
e.g. [133] = 13.3V