48 Reference & Installation Manual
If the Access Control feature is enabled in the system and
the option Door Access during Clock Loss is
ON (section
[537] option [8]), only the System Master Code and user
codes with the Master feature enabled will be able to
program the clock. Enter the System Master or a Master
Code, press [
TRBL], then continue with the steps above.
16.8 Trouble Latch
SECTION [504]: OPTION [6]
(Default: OFF) With the Trouble Latch feature disabled, when a
trouble occurs and is corrected, the trouble is automatically cleared
and no longer displayed. With the Trouble Latch feature enabled,
the trouble will remain displayed until it is manually cleared by the
user. To clear the trouble, users must enter the keypad’s trouble
display (see section 16.7 on page 47) and then exit the trouble
display. For LCD and LED keypads, press [
CLEAR] to exit. For
Grafica keypads, press the left action key (Back) to exit.
Only troubles that have been corrected can be cleared.
If a trouble has not been corrected, it will continue to
be displayed even if the user tries to clear the trouble
by using the method described above.
16.9 Clear Bell Limit Trouble
SECTION [522]: OPTION [5]
(Default: OFF) When an activated bell output is shorted, a Bell
Current Limit trouble is displayed and can be sent to the monitoring
station. This feature determines how the Bell Current Limit trouble
is cleared.
UL Note: For UL installations, section [522] option [5]
must be enabled (ON).
Only troubles that have been corrected can be cleared.
If a trouble has not been corrected, it will continue to
be displayed even if the user tries to clear the trouble
through the trouble display.
Trouble Description
GROUP [1]: SYSTEM
[1] AC Failure
Power failure detected. The system is
running on the backup battery.
[2] Battery Trouble
The backup battery is disconnected, needs
to be recharged or replaced.
[3] AUX Current Limit
Devices connected to AUX have exceeded
current limits (1.1A). The Auxiliary Output
will shutdown until the trouble is corrected.
[4] Bell Current Limit
The bell or siren has exceeded current
limits (3A). The Bell/Siren Output will
shutdown until the trouble is corrected.
[5] Bell Absent
The bell or siren is not connected. When
the bell output is not used, connect a 1k
resistor across the bell output.
[6] ROM Check Error
The control panel registers a data memory
error. Contact distributor for replacement.
GROUP [2]: COMMUNICATOR
[1] TLM1
The control panel is unable to access the
main telephone line.
[2] Fail to Communicate 1
[3] Fail to Communicate 2
[4] Fail to Communicate 3
[5] Fail to Communicate 4
The control panel tried all assigned
telephone numbers and failed to contact
the monitoring station.
[6] Fail to Communicate PC
The control panel is unable to
communicate with the WinLoad software.
GROUP [3]: MODULES
[1] Module Tamper A module’s tamper switch was triggered
[2] ROM Check Error
A module is experiencing a data memory
error. Contact distributor for replacement.
[3] TLM Trouble
A module is unable to access the
telephone line.
[4] Fail to Communicate
A module failed to communicate with the
monitoring station.
[5] Printer Trouble
The control panel registers a problem with
a printer connected to a Printer Module.
Check printer for problems (paper jam, no
paper, no power, etc.).
[6] AC Failure Module power failure.
[7] Battery Failure Module's battery is disconnected, needs to
be recharged or needs to be replaced.
[8] Supply Output Module has exceeded current limits.
GROUP [4]: COMBUS
[1] Missing Keypad
A keypad is no longer communicating with
the control panel.
[2] Missing Module
A device is no longer communicating with
the control panel.
[6] General Failure
No communication between the devices
and the control panel.
[7] Combus Overload
Too many devices (over 95) are on the
combus.
[8] Combus Comm. Error
The combus is having difficulty
communicating between the devices and
the control panel.
GROUP [5]: ZONE TAMPER
Press [5] to display zone(s) Zones displayed were tampered.
GROUP [6]: ZONE LOW BATTERY
Press [6] to display zone(s)
Zone displayed indicates where a wireless
device’s battery needs to be replaced.
Also, the device’s yellow light will flash.
GROUP [7]: ZONE FAULT
Press [7] to display zone(s)
A smoke detector is experiencing a wiring
problem, needs to be cleaned, or a
wireless device is no longer communicating
with its receiver (supervision loss).
GROUP [8]: CLOCK LOSS
Press [8] to re-program
The time and date were reset to default.
1) Press the [8] key
2) Set the hour and minutes according to
the 24-hour clock (i.e. 9AM is 09:00
and 9PM is 21:00).
3) Enter the correct date according to
yyyy/mm/dd.
4) Press [
CLEAR] to exit.
Option Description
[5]
ON
When an activated bell output is shorted, the Bell Current
Limit trouble will remain displayed until it is manually
cleared by the user. The user must clear the trouble
through the trouble display.
[5]
OFF
When an activated bell output is shorted, the Digiplex
control panel will attempt to reactivate the bell output once
every minute for as long as the bell is activated. The Bell
Current Limit trouble is cleared automatically the first time
the control panel does not detect a short when attempting
to reactivate the bell.
Trouble Description