Digiplex DGP-641 Manual de instalación

Busca en linea o descarga Manual de instalación para Los Sistemas De Control De Acceso De Seguridad Digiplex DGP-641. Digiplex DGP-641 Installation manual Manual de usuario

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 0
Digiplex Control Panel (DGP-848) - V4.1
Reference and Installation Manual
Includes DGP2-641BL/RB Installation Instructions
DGP-848
Vista de pagina 0
1 2 3 4 5 6 ... 67 68

Indice de contenidos

Pagina 1

Digiplex Control Panel (DGP-848) - V4.1Reference and Installation ManualIncludes DGP2-641BL/RB Installation InstructionsDGP-848

Pagina 2

6 Reference & Installation Manual2.9 Programmable OutputsThe Digiplex control panel comes standard with PGM1 and PGM2. PGM3 to PGM5 are optional.

Pagina 3 - Table of Contents

DGP-848 Control Panel 72.12 Double Zone ConnectionsEnabling the ATZ feature (see section 4.8 on page 16) allows you to install two detection devices

Pagina 4

8 Reference & Installation Manualsmoke detector sends a CleanMeTM signal, the control panel will generate a Zone Fault trouble and if programmed w

Pagina 5 - Introduction

DGP-848 Control Panel 93 Programming MethodsThe Digiplex control panel can be programmed using the WinLoad software, the Paradox Memory Key, or manu

Pagina 6 - Installation

10 Reference & Installation Manual3.6 Level ProgrammingIn the sections requiring Level Programming, only one option can be selected.For LCD keypad

Pagina 7 - DGP-848 Control Panel 3

DGP-848 Control Panel 114 Zone ProgrammingAll detection devices connected to the control panel, keypads and zone expansion modules must be assigned

Pagina 8 - BELL output has

12 Reference & Installation Manual4.1 Zone NumberingSECTIONS [001] TO [048]The Zone Numbering feature allows you to assign any detection device in

Pagina 9 - AUX. OUTPUT = 700mA

DGP-848 Control Panel 13Figure 15: Delayed 24-hr. Fire Zone4.2.8 Standard 24Hr Fire ZoneSECTIONS [101] TO [148]: FIRST DIGIT = AFor details how to co

Pagina 10 - 2.11 Single Zone Connections

14 Reference & Installation Manual4.4.2 Bypass ZonesSECTIONS [101] TO [148]: OPTION [2]Only zones with option [2] enabled can be Manually Bypassed

Pagina 11 - 2.15 Fire Circuits

DGP-848 Control Panel 15Table 5: Hebrew Keypad Letter AssignmentTable 6: Russian Keypad Letter AssignmentTable 7: Special Characters CatalogueTable 8

Pagina 13 - Programming Methods

16 Reference & Installation Manual4.6 Input SpeedSECTIONS [201] TO [216](000 to 255 X 20msec,default: 600ms) The Input Speed defines how quickly t

Pagina 14 - 3.7 Paradox Memory Key

DGP-848 Control Panel 175 Keyswitch ProgrammingThe Digiplex control panel can support up to 8 keyswitch zones in addition to the 48 standard zones.

Pagina 15 - Zone Programming

18 Reference & Installation ManualFigure 19: Example of Keyswitch Numbering5.2 Keyswitch DefinitionsSelect one of the keyswitch definitions (also

Pagina 16 - 4.2 Zone Definitions

DGP-848 Control Panel 195.4.5 Instant Arming (Keyswitch)SECTIONS [149] TO [156]: OPTION [8]This option is identical to Stay arming except that all ar

Pagina 17 - 4.4 Zone Options

20 Reference & Installation Manual6.6 No Movement Auto-ArmingSECTIONS [505], [509], [513], [517]: OPTION [6]If no movement occurs in a partition&a

Pagina 18 - 4.5 Zone Labels

DGP-848 Control Panel 21[221] will not lockout the keypad, the control panel will transmit the Keypad Lockout report code programmed in section [705]

Pagina 19 - DGP-848 Control Panel 15

22 Reference & Installation Manual7 Alarm Options7.1 Bell/Alarm OutputSECTION [500]: OPTIONS [5] TO [8]When a partition generates an alarm, the c

Pagina 20 - 4.8 Zone Doubling (ATZ)

DGP-848 Control Panel 23Regardless of whether the partition is armed or disarmed when a tamper or wire fault occurs, the Zone Fault trouble will appe

Pagina 21 - Keyswitch Programming

24 Reference & Installation Manual8 Event ReportingFigure 20: Event ReportingRelated FeaturesDelay Before Alarm TransmissionSection [256]Pager Fo

Pagina 22 - 5.4 Keyswitch Options

DGP-848 Control Panel 258.1 Reporting EnabledSECTION [521]: OPTION [3] This option will either enable or disable event reporting. With option [3] on

Pagina 23 - 6.5 Timed Auto-Arming

DGP-848 Control PanelTable of ContentsIntroduction... 1Features...

Pagina 24 - 6.10 Keypad Lock-out Feature

26 Reference & Installation ManualSection [680]• Auto Zone Shutdown: a zone communicates more than the programmed number of transmissions in a sin

Pagina 25 - ECTION [504]: OPTION [5]

DGP-848 Control Panel 27Section [718]• WinLoad Access: the panel ended communication with WinLoad• Installer In: installer has entered the programmin

Pagina 26 - Alarm Options

28 Reference & Installation ManualIf the control panel still fails to report to a monitoring station telephone number after reaching the Maximum D

Pagina 27 - 7.5 Keypad Panic Options

DGP-848 Control Panel 29Alarm Restore CodesSection [792]Sets all report codes in sections [655] to [680] with the default values from the Automatic R

Pagina 28 - Event Reporting

30 Reference & Installation Manual9.4 Busy Tone DetectionSECTION [521]: OPTION [6]Option [6] ON = the control panel can immediately hang up if it

Pagina 29 - 8.2 Report Codes

DGP-848 Control Panel 31Figure 21: Ground Start CircuitKissoff: After receiving a handshake from the monitoring station, the control panel activates

Pagina 30

32 Reference & Installation Manual11 PGM Programming Table*Note1: 0 = All partitions enabled in the system (see section 12.5 on page 36)1 = Parti

Pagina 31 - 8.6 Event Call Direction

DGP-848 Control Panel 339 Access Granted0 Door 01 Door 02 Door 03 Door 04 Door 05 Door 06 Door 07 Door 081 Door 09 Door 10 Door 11 Door 12 Door 13 Do

Pagina 32

34 Reference & Installation ManualC Auto Zone Shutdown0 Zone 01 Zone 02 Zone 03 Zone 04 Zone 05 Zone 06 Zone 07 Zone 081 Zone 09 Zone 10 Zone 11 Z

Pagina 33 - Dialer Options

DGP-848 Control Panel 35‡ You must program a remote control button with a Utility Key option.12 System Settings & Commands12.1 Hardware ResetPer

Pagina 34 - Programmable Outputs

Reference & Installation ManualPower Save Mode ... 37Auto Trouble Shutdown ...

Pagina 35 - 10.4 PGM1 Is Smoke Input

36 Reference & Installation Manual12.4 Installer Code LockSECTION [990]Enter 147 into section [990] to lock all programming. When 147 is programme

Pagina 36 - PGM Programming Table

DGP-848 Control Panel 37on the module will begin to flash until the serial number is re-entered into section [952] or the appropriate tamper or unloc

Pagina 37 - DGP-848 Control Panel 33

38 Reference & Installation Manual13 Access CodesThe Digiplex control panel supports 95 user access codes, 1 System Master Code, and 1 Installer

Pagina 38 - Supervision)

DGP-848 Control Panel 3913.5 User OptionsThe User Options define how each user access code can arm or disarm the system. Regardless of these settings

Pagina 39 - 12.3 Battery Charge Current

40 Reference & Installation ManualAccess Control features. This can be used to disable a lost or stolen card without deleting the user access code

Pagina 40

DGP-848 Control Panel 4114 Access ControlAccess control is an industry term for a system that monitors and regulates the passage into and out of pro

Pagina 41 - DGP-848 Control Panel 37

42 Reference & Installation Manualone partition assigned to the door. An “OR” door will arm or disarm only the partitions that it has in common wi

Pagina 42 - Access Codes

DGP-848 Control Panel 4314.10 Global Access Door Features14.10.1 Burglar Alarm On Forced DoorSECTION [537]: OPTION [5]An Access Door can be assigned

Pagina 43 - 13.7 Access Control

44 Reference & Installation Manual15 WinLoad SoftwareThe Winload software is not verified by UL.15.1 Answering Machine OverrideSECTION [441]When

Pagina 44 - 13.8 Multiple Action Feature

DGP-848 Control Panel 4515.9 Call Back FeatureSECTION [522]: OPTION [1]For additional security, when a computer using WinLoad attempts to communicate

Pagina 45 - Access Control

DGP-848 Control Panel 11 IntroductionParadox Security Systems has once again redefined the boundaries of the security industry and is proud to intro

Pagina 46 - 14.8 Holiday Programming

46 Reference & Installation Manual3) Press the [DISARM] key. If the users have access to more than one partition, they can press the key correspon

Pagina 47 - DGP-848 Control Panel 43

DGP-848 Control Panel 47Figure 23: Normal and Confidential Mode16.5.1 Scroll RestartIn Normal mode the keypad will scroll though the status of the di

Pagina 48 - WinLoad Software

48 Reference & Installation ManualIf the Access Control feature is enabled in the system and the option Door Access during Clock Loss is ON (secti

Pagina 49 - User Features

DGP-848 Control Panel 4916.10 Event Record DisplayThe Event Record Display can only be viewed through an LCD or Grafica keypad. The Event Record Disp

Pagina 50 - 16.4 Access Codes

50 Reference & Installation Manual17 Appendix 1: DGP2-641BL/RB Installation Instructions1.0 INSTALLATIONThe DGP2-641BL/RB is connected to the con

Pagina 51 - 16.7 Trouble Display

DGP-848 Control Panel 51Figure 29 : Access Control Connections2.0 PROGRAMMINGProgramming the DGP2-641BL/RB keypad module is simple. Enter Module Pro

Pagina 52 - 16.9 Clear Bell Limit Trouble

52 Reference & Installation Manual3.4 Display Entry Delay TimerSECTION [003]: OPTION [3]The Entry Delay Timer will be programmed to provide the us

Pagina 53 - 16.10 Event Record Display

DGP-848 Control Panel 53battery. In some cases adding an external power supply may correct the situation.1) From Normal Mode press and hold the [0] k

Pagina 54 - 1.0 INSTALLATION

54 Reference & Installation Manualunlocked when the REX device detects movement and users on either side of the door will be able to open the door

Pagina 55 - 3.0 SYSTEM OPTIONS

DGP-848 Control Panel 555.3.4 Door Left Open Pre-Alarm TimerSECTION [011]This timer will trigger the Door Left Open Pre-Alarm before the end of the D

Pagina 56

2 Reference & Installation Manual2 Installation2.1 Location & MountingBefore mounting the cabinet, push the five white nylon mounting studs i

Pagina 57 - 641BL ONLY)

56 Reference & Installation Manual[STAY] - Insert SpacePressing the [STAY] key inserts a blank space in the current cursor position.[FORCE] - Dele

Pagina 58

DGP-848 Control Panel 5718 IndexAAC Power ... 2Access Alarm ...

Pagina 59 - Table 14: Message Programming

58 Reference & Installation ManualDisabledWireless Transmitter Supervision ... 22Disarm with Access Card ...

Pagina 60 - 7.0 PROGRAMMING SECTIONS

DGP-848 Control Panel 59As a 4-wire smoke detector ... 8Connections ...

Pagina 61 - DGP-848 Control Panel 57

60 Reference & Installation Manual19 WarningsFCC WarningsImportant InformationThis equipment complies with Part 68 of the FCC rules subpart D and

Pagina 62

DGP-848 Control Panel 61CL3R, CL3P, or substitute cable permitted by the National Electrical Code, ANSI/NFPA 70.20 WarrantyParadox Security Systems

Pagina 63 - DGP-848 Control Panel 59

62 Reference & Installation Manual

Pagina 65 - Warranty

780 Industriel Blvd., Saint-Eustache (Quebec) J7R 5V3 CANADATel.: 450 491-7444 Fax: 450 491-2313paradox.comPr

Pagina 66

DGP-848 Control Panel 3Figure 3: Digiplex Control Panel PCB LayoutFor UL/C-UL warnings and requirements, see Warnings on page 60.For the hardwire conn

Pagina 67

4 Reference & Installation Manual2.8 Calculating Power RequirementsTable 1: Milliamp Consumption TableSTEP 1: Using Table 1, calculate the total n

Pagina 68

DGP-848 Control Panel 5Figure 4: Sample Power Requirement Calculations If in the above example you were to add an LCD Keypad (110mA) to the 30m (100ft

Comentarios a estos manuales

Sin comentarios