Digiplex DGP-641 Manual de instalación Pagina 27

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 68
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 26
DGP-848 Control Panel 23
Regardless of whether the partition is armed or disarmed
when a tamper or wire fault occurs, the Zone Fault trouble will
appear in the keypad's Trouble Display and the control panel will
transmit the appropriate report code (see section 8.2 on page 25).
Follow Zone’s Alarm Type
[5] OFF and [6] ON
If a partition is armed, the control panel will generate a standard
alarm when a tamper or wire fault occurs. If the partition is
disarmed when a tamper or wire fault occurs, the Zone Fault
trouble will appear in the keypad's Trouble Display and the control
panel will transmit the appropriate report code (see section 8.2 on
page 25).
Audible Alarm
[5] ON and [6] ON
If a partition is armed, the control panel will generate a standard
alarm when a tamper or wire fault occurs. If the partition is
disarmed when a tamper or wiring failure occurs, the appropriate
trouble will appear in the keypad's Trouble Display, the control
panel will transmit the appropriate report code (see section 8.2 on
page 25), and it will generate an audible alarm.
7.4.1 Tamper Bypass Options
SECTION [501]: OPTION [7]
With option [7] enabled in section [501], Tamper Recognition
follows the zone bypass definition. This means that the control
panel will not perform any action if a tamper or wire fault occurs on
a bypassed zone. With option [7] disabled, the control panel will
ignore the zone’s bypass definition and will follow the option set in
section 7.4 if a tamper or wire fault occurs on a bypassed zone.
7.5 Keypad Panic Options
SECTIONS [506], [510], [514], [518]: OPTIONS [1] TO [6]
Since the control panel can enable Keypad Panic Options for each
partition, select the section that corresponds to the desired partition
and set options [1] through [6] on/off to obtain the desired options.
Sections [506], [510], [514], and [518] represent partitions 1 to 4
respectively.
Panic 1:
Option [1] ON/OFF= Enabled/Disabled
Option [4] ON = Panic 1 is Audible
Option [4] OFF = Panic 1 is Silent
For LCD keypads: Press and hold keys [1] and [3] simultaneously
on the LCD keypad for 2 seconds to generate a Panic 1 alarm.
For Grafica keypads: Press and hold the key on the Grafica
keypad for 2 seconds to generate a Panic 1 (Medical) alarm.
Panic 2:
Option [2] ON/OFF= Enabled/Disabled
Option [5] ON = Panic 2 is Audible
Option [5] OFF = Panic 2 is Silent
For LCD keypads: Press and hold keys [4] and [6] simultaneously
on the LCD keypad for 2 seconds to generate a Panic 2 alarm.
For Grafica keypads: Press and hold the key on the Grafica
keypad for 2 seconds to generate a Panic 2 (Auxiliary) alarm.
Panic 3:
Option [3] ON/OFF= Enabled/Disabled
Option [6] ON = Panic 3 is Pulsed (Fire)
Option [6] OFF = Panic 3 is Silent
For LCD keypads: Press and hold keys [7] and [9] simultaneously
on the LCD keypad for 2 seconds to generate a Panic 3 alarm.
For Grafica keypads: Press and hold the key on the Grafica
keypad for 2 seconds to generate a Panic 3 (Fire) alarm.
Silent Operation
The control panel emits a single Confirmation Beep and transmits
the appropriate report code (see section 8.2.5 on page 25) to the
monitoring station.
Audible Operation
The alarm output (bell/siren) activates until a user cancels the
alarm with a valid user access code or when the Bell Cut-Off Timer
elapses (see section 7.2).
Fire Operation
Same as audible operation, except that the bell/siren output will be
pulsed as shown in Figure 16 on page 13.
Vista de pagina 26
1 2 ... 22 23 24 25 26 27 28 29 30 31 32 ... 67 68

Comentarios a estos manuales

Sin comentarios